1、Chip to Data Center Thermal Resistance to Support 30CAMDChip to Data Center Thermal Resistance to Support 30CPaul ArtmanFellow System Design Eng AMDCOOLING ENVIRONMENTSSOC Temperature InputsJunction Temperature CalculationPowerTla+JCCA+xJunction Temperature=Tjunc=Tla+P x(JC+CA)TCS for Direct Liquid

2、Cooling(DLC)TCS=Chiller/Cooler=FWSAir Temperature=A-Class+CDU ApproachLiquid Cooled DCASHRAE Facility Water Supply(FWS)Coolant Distribution Unit(CDU)ApproachASHRAE Technical Coolant Supply(TCS)Temperature Ranges17 to 45 C2 to 10C25 to 50CAir Cooled DCASHRAE Air Classes(A-Class)Coolant Distribution U

3、nit(CDU)ApproachASHRAE Technical Coolant Supply(TCS)Temperature Ranges25 to 45C5 to 17C35 to 50CThere are a Broad Range of TCS Temperatures1.40+C-Legacy DLC and Brown Field DC using Liquid to Air CDU2.30C-Colocation and Green Filed DC using Liquid to Liquid CDUs3.20C Future NeedTechnical Coolant Sup

4、ply(TCS)=Inlet TemperatureOCP Min Recommended Technical Fluid Temperature of 30CNvidia,Intel,AMD,MSFT,Samsung,&MetaASHRAE TCS Classes.ASHRAE is adding S20 and S25ASHRAE added S25.Ongoing discussion son adding S20Courtesy MPDI:https:/ MPDI:https:/ economizer Water-side economizer New data center buil

5、ds are primarily using chillersEconomizers improve operational energy efficiency of data centers using chillersWater-side economizers bypassmechanical chillers when outside ambient keeps tower water cooler than chillerWater-side Economizers Coolant Distribution Unit(CDU)Types8In-Row1.5+MW at 4C appr

6、oach100kW at 5C approach Liquid to Refrigerant180KW at 15C approachLiquid to Air400KW at 4C approachPerimeter7MW at 4C approachLiquid to LiquidLiquid to LiquidIn-RackLiquid to LiquidNote:CDUs today provide 1.2 to 1.5LPM/KW;future GPUs may require 2.0 LPM/KW at 50psiDLC will quick

word格式文档无特别注明外均可编辑修改,预览文件经过压缩,下载原文更清晰!
三个皮匠报告文库所有资源均是客户上传分享,仅供网友学习交流,未经上传用户书面授权,请勿作商用。
根据报告的内容,全文主要内容概括如下: 1. **热管理技术**:文章讨论了芯片到数据中心的热阻和散热技术,包括直接液体冷却(DLC)和空气冷却系统。 2. **温度范围**:技术冷却供应(TCS)温度范围从17°C到45°C不等,取决于冷却系统类型。 3. **冷却单元(CDU)类型**:包括行内、周边和机架式CDU,以及液体到液体和液体到空气的冷却方式。 4. **冷板性能**:讨论了不同冷板技术的性能,如单相和两相冷板。 5. **冷却技术趋势**:指出DLC性能将趋于饱和,并强调了液体DLC的扩展需求。 6. **性能与限制**:提到2相冷板性能优于单相,但存在预冷和冷凝温度限制。 7. **行业合作**:强调了行业合作和标准制定的重要性,如UQD/UQDBv2规范和PG25兼容性工作。 核心数据: - TCS温度范围:17°C至45°C - CDU流量:1.2至1.5LPM/KW(未来可能需2.0 LPM/KW) - 冷板性能:单相冷板30°C和40°C,两相冷板30°C - GPU TDP功率:TBDEnhanced Single Phase Coldplate 30C*和40C*