1、Data Center High Voltage DC Distribution 2Data Center High Voltage DC Distribution RACK&POWERKelvin HuangHW Dev DirectorAzure Hardware System and Infrastructure MicrosoftLaurentiu OlariuRack and Power ArchitectAzure Platform ArchitectureMicrosoft3AC busway+whips“Yesterday”and“Today”AC Voltage Distri

2、bution To RackATS/breakersUPS AC/DC+DC/ACMVAC to LVAC transformer4AC busway+whipsBreaking Down The“Yesterday”and“Today”LossesATS/breakersRow level UPS AC/DC+DC/ACMVAC to LVAC transformerAC distribution to IT racks480Vac protection480Vac to DC and back to 480Vac4%-6%loss13.8kVac to 480Vac2%loss2%8%-1

3、0%loss5“Yesterday”IT Rack Power Distribution EffectAC distribution to IT racks480Vac protection480Vac to DC and back to 480Vac4%-6%loss13.8kVac to 480Vac2%loss2%lossIT Rack PSU 480Vac 50Vdc2%-3%loss10%-13%loss6“Today”IT Rack Power Distribution EffectAC distribution to IT racks480Vac protection480Vac

4、 to DC and back to 480Vac4%-6%loss13.8kVac to 480Vac2%loss2%lossDiablo 400 480Vac +/-400Vdc or 800Vdc2%-3%lossIT Rack DC/DC+/-400Vdc or 800Vdc 50Vdc2%loss12%-16%loss7MVAC to MVDC via Solid State Transformer(SST):Replaces traditional transformer+UPSProvides direct medium-voltage DC output from AC inp

5、utSignificantly reduces conversion stepsDC Protection&Breakers:Ensures safety in MVDC distribution pathDC Busway+Whips to Rack:Direct delivery of MVDC(e.g.,800VDC)to the IT rackEliminates need for local AC distributionDC voltage distribution busway+whips“Tomorrow”DC Voltage Distribution To RackDC vo

6、ltage protection/breakersMVAC to MVDC Solid Stat Transformer(SST)8Breaking Down The“Tomorrow”LossesDC distribution to IT racksMVDC protectionSST MVAC to MVDC(800Vdc)3%-4%loss2%DC voltage distribution busway+whipsDC voltage protection/breakersMVAC to MVDC Solid

word格式文档无特别注明外均可编辑修改,预览文件经过压缩,下载原文更清晰!
三个皮匠报告文库所有资源均是客户上传分享,仅供网友学习交流,未经上传用户书面授权,请勿作商用。
根据标记内容,全文主要概括了数据中心高压直流配电系统的演变和效率提升。以下是关键点: 1. **“昨日”系统**: - AC电压分布到机架,损耗4%-6%。 - IT机架PSU损耗2%-3%。 - 总体损耗13.8kVac到480Vac为2%,480Vac到DC和回转为4%-6%。 2. **“今日”系统**: - 使用Diablo 400进行480Vac到±400Vdc或800Vdc转换,损耗2%-3%。 - IT机架DC/DC转换损耗2%-4%。 - 总体损耗3%-4%。 3. **“明日”系统**: - 使用固态变压器(SST)将MVAC转换为MVDC,损耗5%-6%。 - IT机架DC/DC转换损耗2%-4%。 - 总体损耗7%-10%。 4. **创新与效率**: - SST取代传统变压器和UPS,减少转换步骤。 - 直流保护与断路器确保安全。 - 直流配电总线直接将MVDC输送到机架,消除本地AC配电需求。 5. **能源存储**: - “今日”使用Diablo 400和机架级存储。 - “明日”在SST中嵌入存储,或在机架间提供冗余或削峰填谷。