1、Classified by Alfa Laval as:BusinessGemma Reeves,Alberto Petermann,Omer WilsonOCP-Aligned Seawater Cooling and Heat Reuse:Enabling Circular Infrastructure for High-Density ComputeClassified by Alfa Laval as:BusinessOCP-Aligned Seawater Cooling and Heat Reuse:Enabling Circular Infrastructure for High

2、-Density ComputeGemma Reeves,Alberto Petermann&Omer Wilson SustainabilityClassified by Alfa Laval as:BusinessSpeakersGemma ReevesGlobal Business Development ManagerAlfa LavalAlberto PetermannHead of Design and DeliveryStart CampusOmer WilsonChief Marketing OfficerStart CampusClassified by Alfa Laval

3、 as:BusinessData center cooling accounts for 4050%of total energy consumption.Leveraging seawater as a cooling medium can reduce cooling system energy use by approximately 30%,while eliminating the need for freshwater.The waste heat recovered from GPU-based AI clusters may then be repurposed to powe

4、r a highly efficient membrane distillation(MD)system for desalinating seawater,producing ultra-pure water.IntroductionClassified by Alfa Laval as:BusinessFollowing the white paper published last year exploring potential savings(both economical and carbon)from utilisingsea water in a GW sized Data ce

5、ntre this second stage POC will be exploring opportunities to utilisethe heat produced from the servers to create potable water.The SeaTech Center at Florida Atlantic Universitys Dania Beach campus has an existing seawater intake system drawing from the Atlantic Ocean.Currently used for marine corro

6、sion testing,this infrastructure can be leveraged to support a circular seawater-cooled AI data center prototype.BackgroundClassified by Alfa Laval as:BusinessCondensate purity allows use in high-spec applications:Boiler feed(anti-scaling)Cooling systems(chloride corrosion risk)Food and beverage pro

word格式文档无特别注明外均可编辑修改,预览文件经过压缩,下载原文更清晰!
三个皮匠报告文库所有资源均是客户上传分享,仅供网友学习交流,未经上传用户书面授权,请勿作商用。
根据报告的内容,全文主要内容概括如下: - **数据中心冷却节能**:使用海水冷却数据中心可减少约30%的冷却系统能耗,并消除淡水需求。 - **热能回收利用**:从服务器回收的热能可用于驱动高效的反渗透系统,从海水中制取超纯水。 - **技术规格**:50kW AI集群使用30°C海水冷却,产生的冷凝水导电率低于1.5 μS/cm,适用于高纯度工业应用。 - **经济效益**:预计年节能约131,400 kWh,淡水产出约1.5 m³/天,投资回报期估计为2-3年。 - **项目进展**:正在进行概念验证(POC),计划2025年第四季度进行测试安装,2026年第二季度发布初步结果。 - **合作与扩展**:与Alfa Laval、RN Solutions和FAU合作,探索循环海水冷却基础设施的可能性,并寻求设施或产品的集成机会。