当前位置:首页 > 报告详情

数据中心设计中的水能关系.pdf

上传人: 明**** 编号:1011900 2025-12-21 13页 1.60MB

1、Rishab Vardhan Harikrishnan OracleMichael Anderson PE SPX Cooling TechnologiesWater Energy Nexus in Data Center DesignWater Energy Nexus in Data Center DesignRishab Vardhan Harikrishnan OracleMichael Anderson PE SPX Cooling TechnologiesSustainabilityData Center:Rising Temperatures and Heat LoadsServ

2、er Temperatures rising to 131F(55C)Server Heat Loads rising while Facility Roofs are already filled with HVAC equipmentRack heat loads now 120kW and going to 600kW(171 Tons)by 2027,Google to 1MWCommercial BuildingData CenterTonsSq FtT/SFData Centers are x8000 the density vs standard Commercial Facil

3、ities14000.0025171821Data Center Customer:Minimize ResourcesPower2X growth to 4%of Global Power by FY28WaterWater Tradeoffs Made to meet Power GapsFootprintRoofs already full of HVAC need higher density equipmentChallenge of Removing Heat from the Data HallIncreased density is making no water usage

4、and net positive ESG commitments more challenging Focus has been on power and better quantifying PUECloser examination of WUE and where to draw boundary linesCloser look at water efficiency metricsOCP water efficiency workstreamThe Green GridASHRAE 90.4IAPMO*Overall Water Risk wri.orgA typical hyper

5、scale data center can use as much water as a city of 30,000 people!“Water for cooling”isnt just a utility billits an ecological risk in stressed regions.Why Water Matters for Data CentersDefinition:Industry standard metric for on-site water use efficiency in data centers=OnSite Water Usage(L)IT Equi

6、pment Energy(kWh)Focus:Measures only direct cooling water useTraditional WUE only scratches the surfacemost water may be“off the balance sheet.”Traditional WUE Water Usage EffectivenessExample 1:Two Data Centers,Same Design Very Different Water RealitiesBoth have identical operat

word格式文档无特别注明外均可编辑修改,预览文件经过压缩,下载原文更清晰!
三个皮匠报告文库所有资源均是客户上传分享,仅供网友学习交流,未经上传用户书面授权,请勿作商用。
根据报告的内容,全文主要内容概括如下: 1. 数据中心面临温度和热负荷上升的挑战,服务器温度可达131°F(55°C),热负荷不断增加。 2. 数据中心密度远高于商业设施,预计到2027年,机架热负荷将从120kW增加到600kW(171吨),谷歌甚至达到1MW。 3. 数据中心用水效率成为关键,一个典型的超大规模数据中心用水量相当于一个3万人口城市的用水量。 4. 传统的水使用效率(WUE)仅衡量直接冷却用水,而WUE+考虑了能源生产中的隐含用水和区域调整。 5. WUE+的公式包括隐含用水、区域调整系数和再利用效率。 6. WUE+有助于在本地化水平上平衡用水和电力效率,OCP水效率工作组定期讨论改进措施。
"数据中心水效新标准" 数据中心的节水新指标" 数据中心如何更绿色?"
客服
商务合作
小程序
服务号
折叠