1、Address1835-B Kramer LaneSuite 2-180Austin,TX 78758WOptimizing Data CenterCoolingTCO&Design Comparisons Between 1P&2P D2C FacilitiesScope&MethodologyJacobs Engineering created two,10MW reference designs of 1P&2P D2C facilities,to help evaluate the technologies cost and performance.Reference Design R

2、equirements Comparable cooling performance at the chip Universal cold plate/vaporator Heat rejection operational limits of 5-40C Everything else held constant(i.e.building,electrical,air cooling)Key Characteristics 10MW of ITE 64 x 136 kW rackso 78%liquid cooled,22%air cooled Two facility water loop

3、s(air&liquid)Concurrently maintainable infrastructureTwo-phase D2Cs thermal performance reduces chiller load requirementsSingle-PhaseD2CTwo-PhaseD2C16 FanHigh Temperature Chillers12 FanHigh Temperature ChillersMR250s integrated manifolds eliminates need for TCS,reducing cost and complexitySingle-Pha

4、se D2CTwo-Phase D2CChip-to-chiller infrastructure has comparable CapEx and Lower OpEx,leading to a 5-year TCO savings of 10%for 2P D2CCapExSingle-PhaseD2C$10,385,576$1,043,799$15,604,571Two-PhaseD2C$10,381,534$678,640$13,774,735Savings(%)0%-35%-12%Annual OpEx5-Year TCO*TCO analysis is based on a dat

5、a center in Austin,TX.Detailed energy consumption for Austin,TX and other regions is available on request.Additionally,the TCO analysis includes maintenance and piping material costs from other third-party sources.Solutions for Every Data CenterMR250LSS&TSRIR80An in-rack two-phase,direct-to-chip coo

6、ling solution.Enables up to 80 kW of liquid cooling capacity per rack.End Users:Enterprise,Colocation Compute:B200/B300 and MI355x servers,CPU servers An in-row,multi-rack two-phase,direct-to-chip cooling solution.Provides 2 x 125 kW or 1 x

word格式文档无特别注明外均可编辑修改,预览文件经过压缩,下载原文更清晰!
三个皮匠报告文库所有资源均是客户上传分享,仅供网友学习交流,未经上传用户书面授权,请勿作商用。
根据报告的内容,全文主要内容概括如下: - **研究背景**:Jacobs Engineering创建了两种10MW的1P和2P D2C设施参考设计,以评估其成本和性能。 - **设计要求**:包括可比的芯片冷却性能、通用冷板/蒸发器、5-40°C的热排放操作限制,其他条件保持不变。 - **关键特性**:10MW的IT设备,78%液冷,22%风冷;两个设施水回路;可同时维护的基础设施。 - **性能比较**:两相D2C的热性能降低制冷机负载需求。 - **成本效益**:两相D2C的资本支出(CapEx)和运营支出(OpEx)较低,5年内TCO节省超过10%。 - **解决方案**:提供多种数据中心冷却解决方案,如MR250 LSS & TSRIR80、R80等,适用于不同规模和需求的数据中心。 - **应用领域**:适用于企业、托管、超大规模计算、研发、解决方案测试和现场调试等。