1、Jared HuntingtonMike Tu800 VDC MGX Accelerated Computing Rack&Energy Storage for Improved GPU Power UtilizationLaw of Power800 VDC ApproachSource SideLoad SideServer800V MGX Racks800V Direct to Node800VDC Busbar800 VDC Cable(s)1500 A+ServerDC/DCVRMGPUFuse+HSC800V12V 1VServer54V Busbar54 VDC BusbarSe

2、rverDC/DCVRMGPUFuse+HSC800 VDC12V 1VPower ShelfPower ShelfServerPower Shelf54 VDC800 VDC 125A800V Datacenter800V DatacenterGPU Load SwingsHow much energy?1010010001000010000010000000.0100.1001.00010.000100.0001000.000Volume(cm3)Time(s)Electrolytic CapsIntermediate StorageLithium Ion BatteriesEDPPWL

3、Idle PeriodsWL Long Idle PeriodsWorkload RampUPS+Grid RequirementsWhere to put it?Grid/SourceEnergy StorageIT LoadPSUExample:GB300 Power Shelf ImprovementsBoost PFCDC/DC240 VAC50 VDCDevelop safety standards and operating procedures around 800V+datacentersStandardized method for DC Arc Flash assessme

4、ntDesigning PSU/PFC as a filter as standard practice for GPU applicationsModular energy storage solutions on the rack,row,and datacenter levelCommon collection of utility requirements for industry to design solutionsWhere to find additional information:https:/ to ActionBack Up SlidesTransition to Da

5、tacenterUL&IEC paths for 800 VDC evolving.Limited deployment precedent slows code updates.Need consensus:test procedures,stress factors,validation.Rack disconnects,fuses,breakers,busways,UPS,BESS,etc.all need certification standards.Certification&Compliance ReadinessNo standardized arc flash models

6、for DC.NFPA 70E gaps for DC hazards.Testing and validation methods still evolving.New operational protocols for DC safety needed.Electrical Safety&Risk MitigationBreaker performance and short-circuit limits unresolved.DC fault interruption less predictable tha

word格式文档无特别注明外均可编辑修改,预览文件经过压缩,下载原文更清晰!
三个皮匠报告文库所有资源均是客户上传分享,仅供网友学习交流,未经上传用户书面授权,请勿作商用。
根据报告的内容,全文主要围绕800V直流数据中心架构展开,强调其优势和创新点。以下是关键点: 1. **800V直流数据中心架构**:采用800V直流供电,提高GPU功率利用率。 2. **核心数据**:1500A+电流,800V直流系统,125A电流。 3. **创新点**: - **电源系统冷却**:液体冷却电缆,液体冷却连接器,直接液体浸泡的内部总线。 - **兼容性与效率**:直接与计算机架兼容,无需转换,提高功率效率。 - **简化架构**:2线+G架构,减少铜用量,简化安装和维护。 - **标准化**:1500V直流系统可扩展性,1000V绝缘等级。 4. **挑战与合规**: - **电气安全**:直流电弧闪络模型未标准化,NFPA 70E存在差距。 - **认证与合规**:需要共识、测试程序、应力因素和验证。 5. **未来方向**:UL与IEC路径的演变,新的操作协议。