《Modular Data Center Scope 3 Emissions Cross Laminated Timber (CLT) vs Steel.pdf》由会员分享,可在线阅读,更多相关《Modular Data Center Scope 3 Emissions Cross Laminated Timber (CLT) vs Steel.pdf(17页珍藏版)》请在三个皮匠报告上搜索。
1、MDC Scope 3 Emissions Cross Laminated Timber(CLT)vs SteelDATA CENTER FACILITIESFacilityModular Data Center Scope 3 Emissions Cross Laminated Timber(CLT)vs SteelKarl Rabe,MD,WoodenDataCenter|Co-Lead OCP MDCDavid G.,MD Impleon|Lead OCP HeatreuseWhat is the status quo?Custom ContainerWhat is the issueO
2、CP Hyperscaler have a 90+Scope3 emissions problemHow should MDC Build Now?What are the solutionsGoal of this effortShow ways the out of the Scope3 dilemmaHow does an Optimzed Rack/MDC CompareDo we need net-zero steel?Do we need net-zero concrete?Todo:What is the improvements for a MDCsParameters of
3、ComparisonSteel based Open Rack V2 vs CLT Open Rack V3Compare:WeightVolumeEmbedded CarbonSteel vs.CLTORV2 SteelORV3 CLTVolume in L25126Weight in kg 199116Embedded CO2e kg 301-32.5Detail calculationOpen Rack V2LitersDensity kg/LGewicht kgCarbon per Kg/M GWPEmbedded Carbon kg CO2eSteel257.9197.5120003
4、00Copper0.128.961.075212433.61.492032Sum198.58301.49OPen Rack V3Wood126.80.6582.42-650-82.42Steel47.931.61200048Copper0.178.961.523212433.62.113712Sum115.54-32.31 Timeline for full MDC comparison WhitepaperMailing list:OCP-MDC+subscribeOCP-All.groups.io Sustainability+subscribeOCP-All.groups.ioCall
5、to Action 3M2M1MGSStart spec nowdraftFinalPublishedPresent at Global S.Thank you!Cross-laminated Timber Constructionhttps:/ecodatacenter.se/Boden Type DC ONE,PUE 1,0148Armor-plated wooden infrastructure Tier 4Weather protectionInsulationArmored Steel plateKevlarFire-protective coatingWood(CLT,X-LAM)
6、Fire-protective coatingOutline15mins 12mins preso+3mins Q&A12mins preso 6 slides1.KR Title slide2.KR Wooden Datacenter Design3.KR What are the preferred characteristics of a MDC?High capacity;low overhead;heat reuse?Answer is LC4.KR Existing effort(s)to meet t