当前位置:首页 > 报告详情

超越 ORv3 HPR 母线:利用液冷技术实现下一代 AI 机架功率等级.pdf

上传人: 明**** 编号:1011382 2025-12-21 17页 1.80MB

1、Hal LoketSystem Architect at TE ConnectivityBeyond ORv3 HPR Busbars:Enabling Next Gen AI Rack Power Levels with Liquid CoolingBeyond ORv3 HPR Busbars:Enabling Next Gen AI Rack Power Levels with Liquid CoolingLily Zhang,Product Manager,TE ConnectivityBrian Costello,System Architect,TE ConnectivityRog

2、er Luo,Mechanical Engineer,TE ConnectivityDmitriy Shapiro,Mechanical Engineer,MetaJohn Fernandes,Thermal Engineer,MetaHal Loket,System Architect,TE ConnectivityDATA CENTER(DC)PHYSICAL INFRASTRUCTUREBackground Liquid cooled busbar design conceptTesting&simulation dataSafety criteria&testingCall to ac

3、tionOverviewRack level power requirements continue to riseAI load requirements already exceeding air cooling limits for ORv3 HPRLatest GPU releases require liquid coolingIncorporate liquid cooling technology to the busbar by leveraging existing infrastructure LC busbar increases current carrying cap

4、acity in same footprint by 5xAllows for improved thermal performance of mating busbar connectorsORv3 HPR BackgroundRack Power(kW)0200400600800100012001400160018002000ORv2ORv3ORv3 HPR2027 AI Racks 2029 AI RacksDesign Considerations Temperature rise-30C MaxVoltage drops-0.1V MaxThermal Interface Mater

5、ial-Thermal conductivity,electrical insulation,ease of assemblySafety-No contact between liquid and copperServiceability-Quick connectionsMass-Reduce as much as possibleReliability-No leakageCold Plate Design-Maximize cooling capability,maintain manufacturability and qualityHose Connections-Standard

6、ization,supply chain,ease of assemblyRack Mounting&Disruption-Maintain profile as close as possible to standardLiquid Cooled Busbar Design OverviewWarm Coolant Outlets(Shown at the Top)Chilled Coolant Inlets(Shown at the bottom)Full Rack HeightVertical BusbarCoolant Channel for Ground Return BusbarC

word格式文档无特别注明外均可编辑修改,预览文件经过压缩,下载原文更清晰!
三个皮匠报告文库所有资源均是客户上传分享,仅供网友学习交流,未经上传用户书面授权,请勿作商用。
根据报告的内容,全文主要内容概括如下: - **背景**:随着AI和GPU负载增加,现有空气冷却系统已无法满足ORv3 HPR机架的功率需求。 - **解决方案**:采用液体冷却技术,通过液体冷却母线(LCBB)提高电流承载能力,实现更高的功率密度。 - **设计要点**:温度上升不超过30°C,电压降不超过0.1V,确保液体与铜无接触,易于维护和安装。 - **性能提升**:LCBB相比空气冷却母线,电流承载能力提高约5倍,允许更高的功率密度。 - **测试数据**:模拟和物理测试表明,液体冷却可提高约1.5倍的电流承载能力。 - **安全性**:通过高压试验和气体泄漏测试确保安全。 - **未来展望**:开发OCP设计规范,进一步优化设计以支持更高功率和更复杂的系统。