当前位置:首页 > 报告详情

用于管理OCP液冷设备的统一Redfish方案.pdf

上传人: 明**** 编号:1011359 2025-12-21 11页 996.96KB

1、Mick JonesUnified Redfish Schema for Managing OCP Liquid Cooling Equipment Unified Redfish Schema for Managing OCP Liquid Cooling Equipment Mick Jones-VertivLIQUID COOLINGDefine a unified schema under DMTF Redfish for management of all OCP Liquid Cooling Equipment:CDUs,Immersion;Tank and Enclosed Ch

2、assisCold Plate;BMCs,aggregation and control loops,Rear Door HXFacilities;FWS,valves,inline sensors,Chillers#,etcHeat Re-use;Tanks/Reservoirs,Heat Exchangers,Pumps,etcCreate mockup(examples)of the expected output from the compliant management interfaces and management systemsContribution schema and

3、mockups to Redfish Forum for inclusion in Redfish releaseCreate/extend OCP Interoperability ProfilesPurpose of WorkstreamThermal Equipment Schema amendments v1.0 were released in 2023.1Release includes schema files and mockupHas 80%coverage of all resources and relationships discussed(v1.0)Thermal E

4、quipment Schema amendments v1.0+were released in 2023.3Adds cooling redundancy resourcesThermal Equipment Schema amendments ongoingIterate schema based on feedbackMessage registriesInterop Profiles and mock-upsProgressPublished in Redfish v2023.1Enhanced in v2023.3In sustaining mode nowSchemaTargeti

5、ng release in Redfish v2024.4(end of year)New messages exclusively for Liquid CoolingExamples:Flow ratePressureFan SpeedPump SpeedLeak detectionMessage Registries New baseline and device profiles based of new Redfish Service Baseline Defines standard interface for a LC device Milestones:Device/syste

6、m Profiles:CDU,Door HX,DLC,Immersion tank,Enclosed chassis Released Profiles list:Redfish Service Baseline-Liquid Cooling Baseline-CDU profileWIP Profiles list:Immersion Cooling Baseline-Immersion Tank ProfileInteroperability Profiles AI Orchestration is drivi

word格式文档无特别注明外均可编辑修改,预览文件经过压缩,下载原文更清晰!
三个皮匠报告文库所有资源均是客户上传分享,仅供网友学习交流,未经上传用户书面授权,请勿作商用。
根据标记内容,全文主要概括如下: - **统一方案**:定义了统一的红鱼(Redfish)方案,用于管理所有OCP液体冷却设备,包括CDU、冷板、BMC、冷却设施等。 - **发布版本**:2023.1版本发布了热设备方案修订版v1.0,覆盖了80%的资源关系;2023.3版本增加了冷却冗余资源。 - **未来计划**:目标在2024.4版本中发布新的液体冷却消息和注册表,包括流量、压力、风扇和泵速度等。 - **互操作性**:创建OCP互操作性配置文件,推动“即插即用”功能,支持AI负载。 - **Redfish优势**:液体冷却基线配置文件发布,CDU、沉浸式冷却罐、机架PDU等设备支持Redfish。 - **参与方式**:鼓励提交反馈、参加会议、提供管理需求输入和专业知识。