1、Cihan Aydin,Sen.Electrical Engineer,Delta Energy SystemsHarry Soin,Senior Director,Advanced EnergyRequirements/Considerations ofNext Generation ORv3 PSU and Power ShelvesRequirements/Considerations ofNext Generation ORv3 PSU and Power ShelvesCihan Aydin,Sen.Electrical Engineer,Delta Energy SystemsHa

2、rry Soin,Senior Director,Advanced EnergyDATA CENTER(DC)PHYSICAL INFRASTRUCTUREComparison ORV3 to ORV3 HPR(High Power Rack)to HPR2 PSU.Cihan AydinMajor Differences ORV3 to ORV3 HPR/HPR2 PSUPeak Shaving ShelfORV3 HPR Efficiency curveOutline Features.Harry SoinPF/iTHD in Dynamic loadsInput Power limit

3、ChangeAuto Input power adjustNext Gen PowerAgendaComparison ORV3 HPR PSU to ORV3 HPR2ORV3 HPRORV HPR2Input Voltage range180 305Vac180 305VacOutput PowerDefault:49V/112ADefault:49V/244AEfficiency(incl.Fan power losses)97.5%peak ;96.5 100%load97.5%peak ;96.5 100%loadOperating Temperature-5 +45-5 +35 S

4、ize L x W x H640mm(L)*73.5mm(W)*40mm(H)790mm(L)*83.4mm(W)*40mm(H)CoolingInternal fanInternal fanMajor Differences ORV3 to ORV3 HPR/HPR2Power increase from 33kW to 72kW within same shelf outer dimensionsTransition to BBUTransition method changed from a output voltage drop by 3V to a AC_LOSS signal fr

5、om PSU Shelf to BBU Shelf to activate BBUsPulse load requirement updated to latest AI GPU requirements 160%/136%PMM(Power Monitoring Module)with dedicated uC to collect data from PSUs&BBUsShelf output connector(barclip)with integrated NTC for temperature reporting and protectionVbustimeV_BBU_trigger

6、 48.5V48VPSU runs for 20ms FLBBU runs up to 240sstart of ac outageBBU starts in 4msecPSU voltage drops by 3V after its holdup energy is lost by 50%BBU startsNote1:all numbers with+/-0.25%accuracy.Note2:PSU and BBU voltage droop is 0.5V for 0-100%load.Note3:BBU is triggered after Vbus is 48.5V for 2m

word格式文档无特别注明外均可编辑修改,预览文件经过压缩,下载原文更清晰!
三个皮匠报告文库所有资源均是客户上传分享,仅供网友学习交流,未经上传用户书面授权,请勿作商用。
根据报告的内容,全文主要讨论了下一代数据中心电源系统的要求和发展趋势,特别是ORv3系列电源单元和电源架的设计与性能。以下是关键点: 1. **ORv3系列电源比较**: - ORV3 HPR PSU与ORV3 HPR2 PSU在功率、尺寸和效率上有所不同。 - ORV3 HPR PSU功率从33kW提升至72kW,而ORV3 HPR2 PSU保持49V/244A。 2. **效率与性能**: - ORV3 HPR效率峰值97.5%,满载时96.5%。 - ORV3 HPR2 PSU在100%负载下的效率为96.5%。 3. **温度与尺寸**: - ORV3 HPR操作温度为-5℃至+35℃,尺寸为790mm x 83.4mm x 40mm。 - ORV3 HPR2 PSU操作温度为-5℃至+45℃,尺寸为640mm x 73.5mm x 40mm。 4. **峰值削峰架**: - 能量存储系统帮助减少AC PSU的输入侧功率峰值,提高系统可靠性。 5. **PMM(电源监控模块)**: - PMM监控PSU或BBU模块的状态,提供Modbus服务。 6. **数据中心电源趋势**: - 从5.5kW到300kW+的HVDC,数据中心电源系统不断升级。 7. **参与社区**: - 参与社区对于下一代电源规格的成功至关重要。