当前位置:首页 > 报告详情

不同冷板方向下的高性能两相冷却.pdf

上传人: 明**** 编号:1011315 2025-12-21 10页 1.32MB

1、OCP EMEA Summit 29 April|Dublin,IrelandDr.Richard Bonner and Dr.Qingyang WangHigh-Performance Two-Phase Cooling under Different Cold Plate OrientationsMarket Need for Different Two-Phase Cold Plate Orientation600kW Racks are Coming with New Architectures!Two-Phase CDUs enabling 250kW+RacksTwo-Phase

2、Cold Plates for 4,500W TDP ProcessorsOrientation based Two-Phase Cold Plate PerformanceSummaryOverviewTwo-Phase cooling performance is required for next gen architectures approaching 600kW in 2027250kW per Rack and 4,500W TDPs demonstrated with two-phase coolingNext Gen architectures will rotate ser

3、vers 90 to maximize power densityTwo-Phase cooling is potentially orientation sensitive due to liquid-vapor phase separationThe Market NeedLiquid Cooled Kyber Rack with Vertical Servers Setfor Deployment 2027,Per NVIDIA at GTCMarch 2025Two-Phase cooling CDU products have recently been released(April

4、 2025)These products can cool 250kW of H100 servers using 40C Facility WaterTwo-Phase Cooling 250kW RacksH100 Junction Temperature(C)CDU Power(kWs)Testing 250kW Racks250kW Thermal Simulation Rack(L)and 5kW Load Simulation Sled(R)Test was run using R515B as the working fluid on a GPU TTVSaturation te

5、mperature was maintained at 40C4,500W was removed efficiently before wall power limitations were reachedNote:Tcase,max the same as Tcase,avg for two-phase due to inherent isothermality Two-Phase Cooling 4,500W TDP ProcessorsProcessor Power/TDP(Watts)Cold Plate Case Temperature(C)Testing same cold pl

6、ate and thermal test vehicle,just rotatedVertical outperforms slightly at higher powersHorizontal upward outperforms slightly at lower powersAll orientations and powers show impressive performancesOrientation DependencyTwo-Phase Cooling pro

word格式文档无特别注明外均可编辑修改,预览文件经过压缩,下载原文更清晰!
三个皮匠报告文库所有资源均是客户上传分享,仅供网友学习交流,未经上传用户书面授权,请勿作商用。
根据标记内容,全文主要内容概括如下: - **高性能冷却需求**:下一代架构预计在2027年达到600kW,需要两相冷却技术。 - **市场趋势**:预计2027年将部署液冷Kyber机架,采用垂直服务器。 - **产品发布**:两相冷却CDU产品已发布,可冷却250kW H100服务器。 - **性能测试**:250kW机架和4,500W TDP处理器通过两相冷却有效散热。 - **方向依赖性**:两相冷却在不同方向上表现不同,垂直方向在更高功率下表现更好,水平向上方向在较低功率下表现更好。 - **总结**:两相冷却对250kW机架和4,500W TDP处理器有效,600kW机架需垂直安装服务器。